Reach, Temperature and Humidity Pressure, Flow, Ph Control Specialists
Series PAK
REACH
REACH MICRO PROCESSO TEMPERATURE CONTROLLER
BASIC FEATRUES
 Multi-input and multi-range performance
 Includes a new processing system, Expert PID, remarkably
improved PID control efficiency; overshoot and undershoot
are controlled effectively.
The Keylock function can avoid erroneous operation
resulting from set values or parameter settings.
 High/Low alarm available as basic feature
Display
Digital display:
Parameter display:
Action display:

Display accuracy:


Display accuracy range:
Display resolution:
Measured display range:
Sampling cycle:

Setting
Setting:
Setting range:

Power supply
AC85+0265V 50/60Hz
Power cosumption
About 4VA
Memory element
Eeprom

Process value (PV)/7-segment red LED 4 digits
Set value (SV)/7-segment green LED 4 digits
7-segment LED for PV and SV
Green LED for two points of output (OUT1, OUT2), Yellow LED 3 points For (AT,MAN,PRD)
Red LED for two points of alarm (AL1, AL2)
Within 0.2% of display value +1digit)
Depends on measuring range (0.1, 1)
-10~110% (-210~680J for -200~600J of R.T.D. input)
250MS (0.25 Ses)
By 4 front key switches
Same as measuring range

Input
Tyep of input:

Thermocouple:
External resistance:
Input impedance:
Burnout:
Cold junction temperature
Compensation accuracy:

R.T.D.:
Amperage:
Lead wire tolerable resistance:
Voltage:
Input impedance:
Current:
Receiving impedance:
Input scaling function:
Scaling range:
Span:
Position of decimal point:
Sampling cycle:
PV bias range:
PV filter:
Isolation:

Multiple input of Thermocouple, R.T>D., PT100[& PT150[ Voltage (mV), or voltage, or Current 4~20mA DC by ordering information. Refer to Measuring range code table.
B,R,S,K,E,J,T,N,W,PLII{U,L (DIN 43710)}
100[ max.
500k[ min.
Standard feature (up scale)

2J (5~45J)
(5J to the negative side of measuring range in case of T and U input)
JIS Pt100/JPt100 3-wire type, PT 50 J2s
Approx. 0.25mA
5[ max./wire (The 3 lead wires should have same resistance.)
0~10, 10~50, 0~100mV DC or 0~1, 1~5, 0~10V DC
500k[ min.
4~20mA DC or 0~20mA
250[ max 800[
Scaling possible for voltage (mV, V)
-1999~9999 counts.
10~5000 counts
None, 0.0, 0.00, 0.000
0.5 sec.
20.0 unit in case the decimal point is included in the measuring range. If not, 200 unit. 
0~100 sce. (0=without filter)
Insulated between input and output (not insulated between input and sysem)

Control
Control mode:
Proportional band (P):
Integral time (I):
Derivative time (D):
Manual reset (MR):
On-Off hysteresis:
Proportional cycle:

Auto tuning PID/On-Off control
Off, 0~200 sec. FS (Off setting: On-Off action)
Off, 0~3600 sec. (Off setting: P or PD action)
Off, 0~900 sec. (Off setting: P or PI action) 
-50.0~50.0% (Valid when P=OFF and I=OFF)
0~150 sec.
Fixed to 0~150 sec. During SS drive voltage output

Control output type/rating
Contact output

Current output:
SSR drive voltage output:
Voltage output:
Isolation:

Contact 240V AC 3.0A/resistive load:1.5A/inductive load
Motor Value Control Output 10A/240V AC
4~20mA DC/load resistance: 800[ max.
20V DC (with load resistance at 1.5k[)/load current: 20mA max.
0- 20V DC/load current: 2mA max.
Insulated between control output and system and input

Alarm Output
Number of alarm points:
Alarm Type:

Alarm setting range:
Deviation value:

Alarm action:
Alarm action hysteresis:
Alarm output/rating:

2(AH and AL)(for both normal open and common)
Selectable from combinations of the following 4 types
0.Not assigned
1.Higher limit deviation value + lower limit deviation value without inhibit action
2.Higher limit absolute value + lower limit absolute value without inhibit action
3.Higher limit deviation value + lower limit deviation value with inhibit action
4.Higher limit absolute value + lower limit absolute value with inhibit action
5.Segment end alarm (USE for program only)
6.program end alarm (USE for program only)
7.System error alarm-ON or alarm-OFF
8.Herfer break alarm-)X single phase
9.on delay timer alarm
Higher limit and lower limit absolute value alarms: Within full scale of measuring range
Higher limit:0-9999unit
Lower limit: for input TPE con Range-1999
In case SV is out of the measuring range, higher and lower limit values of the measuring range
Become the action points.
On-Off action
Fixed to 0.2% of the measuring range
Contact 1 (common)/240V AC 1.5A (resistive load)

Others
Date storage:
Operating ambient temperature
/humidity range:
Supply voltage:
Power consumption:
Insulation resistance:

Dielectric strength:

Protective structure:
Material:
External dimensions:
Mounting:
Panel cutout:

Weight:

By non-volatile memory (EEPROM)

-0~50J/90% RH max. (no dew condensation)
85~265 AC 10% (50/60 Hz)
Approx. 2VA
Between input/output terminal and power supply terminal: 500V DC 20M[ minimum
Between input/output terminal and protective conductor terminal: 500V DC 20M[ minimum
1 min. at 2300V AC between input/output terminal and power supply terminal
1 min. at 1500V AC between poser supply terminal and protective conductor terminal
Only front panel has simple dust-proof and drip-proof structure
PPO resin molding (equivalent to UL94V-1)
PAK400:H48W48D96
PAK600:H48W96D96
PAK700:H72W72D96
PAK 800:H96W48D96
PAK900:H96W96D96
Push-in panel (one-touch meunt)
PAK400:H45W45mm
PAK600:H45W92mm
PAK700:H68W68mm
PAK800:H92W45mm
PAK900:H92W92mm
PAK400:300g
PAK600:325g
PAK700:310g
PAK800:325g
PAK900::325g
SR73B:Approx.330g, SR74B: Approx. 250g

ITEMS CODE
SERIES
PAK400-
PAK600-
PAK700-
PAK800-
PAK900-

H48W48D96        digital controller for auto tuning PID control
H48W96D96        digital controller for auto tuning PID control
H72W72D96        digital controller for auto tuning PID control
H96W48D96       digital controller for auto tuning PID control
H96W96D96       digital controller for auto tuning PID control

OUTPUT 1

0
1
2
3
4
5
6
7
8
9

NONE
Relay contact, SPPT 3A/240VAC
Volt, Voltage pulse, 20VDC/20MA
MA, current, 4~20MA
SSR 1A
1X SSR Zero control Driver
3X SSR Zero control Driver
Open loop circuit servo motor control 10A/240VAC
1XSCR PHASE control Driver
3XSCR phase control Driver

OUTPUT 2

0
1
2
3

NONE
Relay contact, SPDT 3A/240VAC
Votf, Voltage pulse, 20VDC/20MA
MA, current, 4~20MA

Alarm

0
1
2
3
NONE
ONE set alarm
TWO set alarm
THREE set alarm (fro PAK900 only)

Transmitter

0
1
NONE
0-20MA (Adjust table)

Second Input

0
1
2

NONE
0-20MA remote set point 1
0-20MA remote set poin 2 This funtion excap 

Communication 

0
1
2

NONE
RS 232
RS 485